Is it okay to daisy chain a UPS?

https://www.eaton.com/us/en-us/support/eaton-answers/daisy-chain-ups.html

By nuker at

chx | 8 comments | 3 weeks ago
Note the last image of the article is not correct, if you want full redundancy you need two independent power feeds. How independent depends on your needs of course. You might just want to run it from a different circuit but the same utility power. If you've got insane needs and megabucks you can talk to the utility about being fed from two substations or at the extreme end you can get one feed from the utility and you can make your own second feed. Traditionally we did this with water turbine working from a river but today I might look into solar and perhaps molten salt.

As an example, way back then when this was a very lucrative business, we placed the servers for a premium number erotic call in an industrial park on the border of two districts in Budapest because that's where we could get two independent power feeds without running our own lines. Internet connection wise, one was a simple leased line the other was a microwave connection to very far away. Short of bombing the entire site it was fair impossible for the installation to go offline and -- for the six years I knew about it, it never did. Note the site served German callers, that's where the big bucks came from.

linsomniac | 4 comments | 2 weeks ago
>run it from a different circuit but the same utility power.

If you're going to come from a different circuit, see if you can at least pull it from a different phase, if we're talking a 120v circuit on 240v service (typical US home service). It's a small improvement, but I'd say 10%+ of the power outages I've seen have been just a single phase going out.

hunter2_ | 4 comments | 2 weeks ago
The center tapped transformer that provides residential split phase 120/240 on its secondary winding connects to just 1 of the 3 grid phases on its primary winding. If that one phase goes out on the grid, both sides of the split phase service go out together. There would need to be a fault on just one side of the split, downstream of that transformer, for your suggestion to hold up. Certainly not impossible, but far less common than a "losing one phase" scenario which would typically originate upstream on the high voltage side.

On a commercial 3 phase service, yes, connect redundant PSUs to separate phases, since each phase on the panel actually corresponds to each phase of the grid.

cesarb | 1 comment | 2 weeks ago
> The center tapped transformer that provides residential split phase 120/240 on its secondary winding connects to just 1 of the 3 grid phases on its primary winding.

I believe that's a USA peculiarity. Where I live, the usual residential and commercial wiring is from 13.8 kV to 127V/220V through a three-phase delta-wye transformer, in which the primary connects between each pair of phases, and the secondary connects between one phase and the neutral (the high-voltage primary side does not have a neutral). When one phase of the high voltage side is lost (very common, since each high-voltage phase is a separate wire and has an independent fuse upstream of the transformer), what happens is that one phase of the low voltage side stays normal (the one between the two intact high voltage phases), and the other two have a lower voltage which varies depending on their relative load.

kelnos | 1 comment | 2 weeks ago
> I believe that's a USA peculiarity.

Yep. Sounds like you have true 3-phase service, whereas most places in the US just get split-phase.

Pet_Ant | 2 comments | 2 weeks ago
Is there a ELIA5 of what this distinction is?
bitfilped | 0 comments | 2 weeks ago
Look up Wye vs Delta; but the basic point is in delta the phases are connected in series with each other, and in wye they are connected in parallel. It's easier to visualize when you can see the tap points on the transformer secondaries though.
Maskawanian | 0 comments | 2 weeks ago
You can definitely loose one phase of a split phase transformer. I've seen it 3 times in my life. Sometimes it is completely out, other times I've seen only getting 80v rather than the full 120.

All depends on how it failed.

kurthr | 1 comment | 2 weeks ago
But if the issue is a local breaker flip, then being on a different phase is very effective!

I don't have a power outage more than once a year, but we manage to blow a breaker more than a few times a decade (vacuum + water boiler was one).

anamexis | 2 comments | 2 weeks ago
If the issue is a breaker flip, then you only need to be on different breakers, right? Phase is irrelevant in that case
hunter2_ | 0 comments | 2 weeks ago
Right, because the main breaker would be 2 pole (or at the very least handle tied).
linsomniac | 0 comments | 2 weeks ago
Generally, yes, but there are some exceptions like different breakers on a shared neutral, which may be tied so that both circuits break.
linsomniac | 0 comments | 2 weeks ago
Agreed, as I said it seems like around a 10% improvement, which considering it's fairly easy to ensure the circuits are on different phases, is worth doing IMHO.
DrPhish | 1 comment | 2 weeks ago
I have also seen a single phase go out (bird poop into a transformer) and having redundant PSUs on different phases saved our bacon
dylan604 | 0 comments | 2 weeks ago
The house I grew up in lost transformers multiple times a year from squirrels.
willis936 | 2 comments | 2 weeks ago
I'm working on a facility with redundant power and my impression is that it's not insanely expensive if you have expensive machinery to protect and that diesel generators are far and away the most common and inexpensive second feed.
xen2xen1 | 1 comment | 2 weeks ago
Worked at a place with a natural gas genny as the second source. You don't have to feed it, it just keeps working.
ocdtrekkie | 1 comment | 2 weeks ago
Technically you are just feeding it power from a different utility company than the electric company.
hedora | 2 comments | 2 weeks ago
I wonder if natural gas is actually redundant at this point. Around here, phone company decided to take a dependency on the power grid, so phone + internet go down if the power is down.

It wouldn't surprise me at all if some utilities have started installing smart meter upgrades or inline compressors or computer-controlled valves that don't have generators attached to them.

wongarsu | 1 comment | 2 weeks ago
> phone company decided to take a dependency on the power grid, so phone + internet go down if the power is down

I hope it goes down a couple hours later?

Around here (Germany) your phone and internet is also dependent on a junction box with routers somewhere within half a mile or so of your home having power. But they have four hours of battery backup, and on normal-sized outages they send people out with diesel generators when the batteries start running low (prioritizing business customers). Having it go down from power loss is a decision made in triage, not something that just happens

tharkun__ | 2 comments | 2 weeks ago
How common are power outages? Historically and in the coming years given nuclear power I hear is dead in Germany and France's reactors are old or need to shut down because of rivers being too hot in summer. Is the 4 hours a 1980s decision that needs revising?

Asking, coz Canada here. Power outages aren't uncommon (when I say that I mean: expect at least one that makes you get out the generator in 'shoulder season' per year), coz power lines (not talking transmission lines) are mostly above ground, except in large cities of course. But as soon as you get out of the "center" (which depending on city is larger or smaller too) it's good old wooden poles that carry power on the top and cable / phone on the lower level.

Bucket transformer[1] on a pole near you blows up is a favourite but the lines are actually fine, including your cable / DSL. Last time we also lost internet it took about 24 hours after power went out that internet went down as well. Cell phone service from the same company was still fine. The entire metro area was out of power for days and I guess they prioritized topping up the diesel/LP for those.

[1] These guys https://en.wikipedia.org/wiki/Distribution_transformer

wongarsu | 1 comment | 2 weeks ago
Large-scale power outages are exceedingly uncommon in Germany, or really all of Europe. The last big one was in 2006 because of some mistakes when taking down a major transmission line [1]. I don't remember reactors being offline ever causing a power outage. When France has to shut down its nuclear reactors Germany just fires up more coal plants, that's the beauty of a large interconnected grid.

What does happen are smaller scale outages. Power lines are mostly buried along streets and under the sidewalk, just like telephone lines. That doesn't stop the occasional excavator digging too deep and taking a street off the grid. At an individual level it's extremely uncommon, maybe once a decade. But deploy thousands of boxes with networking equipment all around the country and it happens to your equipment all the time.

1: https://en.wikipedia.org/wiki/2006_European_blackout

tharkun__ | 1 comment | 2 weeks ago
Yeah historically that makes a lot of sense to me. Reactors going offline directly would usually be planned and thus not cause instability.

The 2006 one I had read about before. I love reading timelines of such disasters. Shows how hard this actually is and how much work it is to keep it all running.

Here's another one: https://en.wikipedia.org/wiki/Northeast_blackout_of_2003#Tim... And speaking of Canada and power lines (this time it does include transmission lines) https://en.wikipedia.org/wiki/January_1998_North_American_ic... While not so severe this is basically the kind of thing I was referring to us happening in "shoulder season". There's usually at least one ice storm or very wet snow event at the start and/or end of winter now and it's very likely that in our wooded area we get trees into power lines and boom the buckets go. When we're lucky it's localized and crews are available to come out and fix it in a few hours. If it's all over the place then it's gonna take a while and they'll have crews from other provinces and the US come in to help as well.

I'd be interested in your outlook on the future of the grid in Germany and Europe though. Of course when France takes a nuke offline, that's usually planned, even when done for a "river water temperature emergency" it's gonna take a while and you can bring that coal plant online like you mention. But doesn't Germany want to reach the climate goals it set itself? How does coal make sense there? And how is shutting down their own nukes a thing when it's OK to use French nuke power?

Or some natural gas, which is quicker. If you have the gas. Re: Russia.

In all of the European (NATO) countries together, is there enough generation capacity if you assume zero Russian inputs (save for say untraceable third party transit or resources) and half of France's nukes going offline? Especially when the sun doesn't shine because bad weather and thus the winds are so high that you have to shut down your wind turbines?

wongarsu | 0 comments | 2 weeks ago
> There's usually at least one ice storm or very wet snow event at the start and/or end of winter now and it's very likely that in our wooded area we get trees into power lines and boom the buckets go

That's where a large, sparsely populated country is a real disadvantage. "Trees into powerlines" isn't really an event in Germany, since high voltage lines are 150 feet up in the air and kept clear of trees (they'll just cut a line though a forest for them). And everything smaller is generally buried. But that would be very hard to do in Canada. And of course we don't have to fight with ice on our transmission lines.

> How does coal make sense there?

Lobbying. And saving the jobs of hard-working coal miners is more romantic and appealing in election campaigns than saving the jobs of wind turbine manufacturers.

It used to make economic sense in the sense that coal plants were cheaper to run, but that has changed in recent years so what you see now is mostly inertia

> And how is shutting down their own nukes a thing when it's OK to use French nuke power?

Oh, there are lots of protests against French nuclear plants too, especially those in the border regions. We just can't do much about them. But the people who don't like nuclear plants aren't the ones running the energy markets.

On the future: Before 2022 the idea was to transition all coal capacity to gas. This was mostly happening on its own anyways due to gas outcompeting coal on price, and new pipelines like Nordstream were going to accelerate that economic pressure to transition. The Ukraine war was a big setback for that.

In the end I believe we are still moving to a future where a lot of power is coming from solar and offshore wind, with natural gas peaker plants to offset times without wind until grid-scale battery technology moves a bit along (molten salt, hot sand, pumped hydro in abandoned mines, etc). In addition to that obviously hydro and pumped hydro from the Scandinavian countries

We are far enough into economies of scale that the generation side is mostly going to sort itself out on economics alone. Solar is becoming dirt cheap, offshore wind is becoming profitable, natural gas is cleaner and cheaper than coal. The bigger issue are transmission lines. Building transmission lines takes decades because every NIMBY fights against them. But the existing transmission lines are built around a somewhat even spread of supply and demand, versus the new situation where we want offshore farms in the North Sea to be able to supply lots of electricity to the South when there's good wind, and the solar panels in the South to help power the North. And politicians from certain parties love to side with "their" NIMBYs for easy political points

20after4 | 0 comments | 2 weeks ago
In small town USA, my cable internet goes offline immediately even if the power outage is just a 1 second flicker. Then takes some equipment to reboot at the cable office before it comes back online. Very annoying. Phone companies typically have a good battery backup though.
bobthepanda | 0 comments | 2 weeks ago
At least during the Texas grid failures during their freeze the other year, gas ended up not being a backup because the lines froze over.

Something is only really a backup if the actual fuel is on site, at this point

michaelt | 4 comments | 2 weeks ago
Diesel generators are great if you need a few hours of backup (assuming the generator actually starts when you call on it).

But if you need enough backup capacity to survive something a multi-state, multi-day blackout [1] that probably gets expensive.

You wouldn't need that for a premium erotic call processor, but a 911 call exchange might, for the portion of their workload they can't pass off to another exchange.

[1] https://en.wikipedia.org/wiki/Northeast_blackout_of_2003

willis936 | 1 comment | 2 weeks ago
You can store about a day's worth of diesel on-site and have agreements in place to have daily refills in cases of emergencies.

If you can't get gasoline within a day's drive then there's bigger problems in the world.

progbits | 0 comments | 2 weeks ago
In many places going over what you can store might put you over emission quotas and you would have to shut down anyway. I'm familiar with one incident at large DC which had fuel left and could easily get more, but only had few hours before they were required to shut down by EPA.
s0rce | 0 comments | 2 weeks ago
I worked at a site where we powered a bunch of stuff consistently from diesel generators until the grid hookup was finished, much longer than a few days. Probably was expensive.
segmondy | 0 comments | 2 weeks ago
Natural gas generators.
j45 | 0 comments | 2 weeks ago
Looking at multi fuel generators is worth it too depending on your setup.

For example some can run gas/propane/natural gas

znpy | 1 comment | 2 weeks ago
> for the six years I knew about it, it never did.

my dude i cannot tell you how much i love these stories of non-faang, real world engineering for extreme reliability.

thank you for posting that.

chx | 0 comments | 2 weeks ago
my fav real world engineering story is of the first commercial ISP in Hungary

back then running leased lines would've been way too expensive. So what did the kids running the show did? They got wind of a central office in an older part of Budapest have excess capacity so they rented an apartment in the next building and drilled the wall :D no expensive trenching, no expensive equipment to demultiplex landlines, nothing, just a bunch of wires running straight from the CO equipment into retail modems... We had no idea what we were doing, mind you. I was already doing Linux at the time so among the few installers I was the lucky guy who got to install the Internet at a small business who wanted it to be done on a Solaris workstation. That was a fun challenge... Other installs were Trumpet Winsock. The ISP itself ran a custom linux app, you dialed in and landed on a text app or maybe it was Lynx? can't quite remember, it's been 30 years...

mcfedr | 1 comment | 3 weeks ago
Presumably that's what they are showing with two wires with different shape connectors
adrianmonk | 0 comments | 2 weeks ago
And/or the box labeled "Utility Power" is not intended to convey any specific notion of single circuits or multiple circuits nor of single substations or multiple substations. It just depicts power that in some way comes from a utility and no more.

In that sense, it is not incorrect about the configuration of utility power because it doesn't say anything about that subject.

j45 | 0 comments | 2 weeks ago
I read the graphic differently and it reads ok to me.

The two different power sources are different shapes.

To someone who’s setup things in datacentres, it seems pretty reasonable to see that could be 2 different circuits.

Of course it should be 2 separate plugs with the 2 different shapes in them.

As for batteries you can just get a UPS system that supports adding extra batteries to it.

myself248 | 0 comments | 3 weeks ago
Another thing they don't mention is that when utility AC returns, each UPS in the chain tries to recharge, which can be a significant chunk of power. Any given UPS is sized so that its downstream load plus its own recharging power doesn't overdraw the circuit, but add two recharging powers and it's much more likely.

I don't think this is an issue with double-conversion UPSs, since their input power is fixed by their rectifier size and they'll simply charge more slowly instead, but with standby type, it's very much a concern.

digitalsushi | 3 comments | 2 weeks ago
I had an underpowered battery backup for my desk, and was using it for my gaming PC, two laptops, and two external monitors, and all my peripherals. (It didnt occur to me I was overrunning it, otherwise my rant here is nonsensical)

The monitors both had the same general issue - they would fail to find a signal every few weeks, and I'd find that waiting a few hours with them turned off would help.

I have pages of notes here. Another way to get them to work would be booting up the windows computer, which would seem to 'trick' the monitor into getting a signal on hdmi, and then I could switch to display port for the mac laptops to be used.

Anyways it's all crazy rambling notes, with copious timestamps, looking for patterns. I have an IR heat thermometer from the kitchen and my monitor vents would regularly have air over 160F coming out the tops when the monitors would not even post the vendor logo after a hard power reset.

I removed the battery backup and it's been months now with zero blips. So the only obvious takeaway I have is that overrunning a battery is a completely worthless endeavor.

lmpdev | 4 comments | 2 weeks ago
What I find insane is the peak current discharge those little 12V 7-9ah backup batteries can push out

Well over 100A for a few seconds

Lithium can’t even do that in a single cell (but in turn is infinitely better for continuous current)

It sort of baffles me intuitively that an extremely simple lead battery can for a short while compete with the grid

somehnguy | 0 comments | 2 weeks ago
Lithium polymer pouch cells can easily push out well over 100A, even relatively small cells hit this mark no problem.
p1mrx | 0 comments | 2 weeks ago
12V x 100A = 1.2 kW. A typical grid connection for a house is 240V x 200A = 48 kW.
jpgvm | 1 comment | 2 weeks ago
Yeah this is why lead acid was hard to replace in cars with lithium chemistries.

The Cold Cranking Amps (pretty much the peak startup current) that they can provide is rather insane. Even my small motorcycle battery provides over 250 CCA.

elintknower | 0 comments | 2 weeks ago
Super capacitors / just large capacitors in general might eventually save the day here. The only issue is super capacitors can't generally bake in the heat all day and still work for 3-5 years like lead acid batteries can.

Supercaps is how "fast" charging in most smartphones works as well since they can soak current faster than the battery itself and also mitigate cycling batteries too hard.

jnsaff2 | 0 comments | 2 weeks ago
It won't be anywhere near 12V while supplying those 100A.
j45 | 1 comment | 2 weeks ago
It might also be helpful to ensure you have a battery backup that provides pure-sine wave electricity when plugged in, and ideally as close to it as possible when on battery backup and the power is out.
jjeaff | 1 comment | 2 weeks ago
most electronics don't need pure sine waves as they are converting the ac to DC anyway. but perhaps a square wave could throw off some PSUs.
j45 | 0 comments | 2 weeks ago
Good point.

I ran a lot of gear through a decent separate PDU and the rack of datacenter gear refused to die. No burst transistors or other things that can be the norm after.

My comment was definitely based in this - providing the cleanest electricity possible, however, doesn't hurt, and can only help.

russdill | 1 comment | 2 weeks ago
Are they Asus monitors by any chance?
digitalsushi | 1 comment | 2 weeks ago
both dells. different series but both dells.
russdill | 0 comments | 2 weeks ago
Ah, there was a line of ASUS monitors that were notorious for bad caps and when conditions were marginal, they'd take forever to get a signal.
rietta | 2 comments | 2 weeks ago
I know from experience that plugging an old school digital alarm clock into a UPS does not work. The clock drifts badly. Turns out those use the AC cycle rate as their clock.
kadoban | 1 comment | 2 weeks ago
It should depend on the UPS, some I believe are indistinguishable from wall power, especially without actually trying.

Even for the cheaper UPSes I wonder if the issue isn't the cycle rate, but the cycle shape? My understanding is that they tend to be able to hit 60Hz pretty easily, but the cheaper ones are a ~square wave instead of a ~sine wave. Maybe the digital clock just glitches on that more.

yafosuda | 0 comments | 2 weeks ago
To clarify this comment: there are two primary types of UPS, double conversion and line interactive.

Double conversion takes power from AC, converts it to DC to charge batteries, takes battery output, and inverts it back to AC. All power drawn from the UPS goes through the battery and inverter stack, and there is no transient/power loss when AC mains are lost. They tend to be more expensive, louder, run hotter, etc.

Line interactive UPSs, on the other hand, tend to be cheaper and are in most cheap consumer products. They take AC mains, convert it to DC, and charge batteries. But AC mains is also connected directly to the output device through switch circuitry that will quickly switch the power source from AC mains to batteries/inverter if power loss is detected.

Reputable UPSs will use pure sine wave inverters for converting DC battery back to AC. Modified sine waves are indeed a lot cheaper but are not suitable for some sensitive equipment.

LorenPechtel | 0 comments | 2 weeks ago
Yup, made a variation of this mistake once long ago. Ordinary clock, plugged into a transformer connected to Chinese (220/50) power. It ran 20% slow.
delichon | 12 comments | 3 weeks ago
I've never found a straight answer on whether it's ok to daisy chain surge protectors. Anyone know? I've been trying to avoid it based on a warning I don't understand, but it can be tough to find power bars without surge protection.
GuB-42 | 1 comment | 2 weeks ago
I don't see the problem, provided that you are within the current draw limits.

Surge protectors are usually made of components that cause a short when a surge happens, protecting the equipment downstream. It usually pairs with some kind of overcurrent protection (breaker, fuse, sometimes GFCI) to protect against the short the surge protector itself caused.

Having chained surge protectors it actually quite common. You may have a surge protector in your breaker panel, then in your powerstrip, then in the power supply of the device you have plugged in. Most good quality ATX power supplies have built-in surge protection for instance. They also all tend to have overcurrent protection too. The breaker panel has breakers (duh), the power strip may have a simple breaker too, and the device may have a fuse. In the UK, the plug itself may have a fuse, plus the breaker from the utility company.

The risk from chaining surge protectors is that it increases the risk of false triggers if one of them is defective. But it may also provide better protection. All in all, I wouldn't worry too much about it. Just don't overload that power bar and whatever it is plugged in.

WarOnPrivacy | 1 comment | 2 weeks ago
> it may also provide better protection.

This has been my experience. There was a corridor between 2 FL counties known for heavy lightning strikes. I serviced small sites that had their IT equip fried (exploded, melted) once or twice a year.

Putting it behind 4-6 decent, consumer-grade surge protectors turned out to be really effective. I was a bit surprised given how lightning can jump over protection during a strike.

To illustrate the area: An XO's home was hit. Char marks lined the walls wherever wiring ran. Pipes burst all over. Nothing plugged in or wired survived. The front door was blow into the street.

His grade school kids were home at the time; they were physically fine.

LorenPechtel | 0 comments | 2 weeks ago
There's also the fact that consumer surge protectors are incapable of determining if they're any good or not. There's a small component in there that eats the surge--a severe surge and it's destroyed, it's obvious. However, there's a range in which it no longer functions but is not destroyed. The next surge goes on down the wire.

I really wish someone would come up with some surge suppressors that have a string of field-replaceable suppressors. Periodic maintenance, replace the suppressors.

AstroJetson | 1 comment | 3 weeks ago
You need to know what the cable size is of the power strip and the current you are going to draw. If you have bar A with 14 ga cable plugged into the wall, and bar C With 18 gauge plugged into that, then with devices that don’t exceed C current rating (12 amps) and devices in A ( including the devices in C ) that don’t exceed A’s rating, you will be fine. The other way wall - C - A is the problem, C isn’t able to manage the full load.

Only buy known surge suppressor, there have been tear downs where the surge components were missing / fake.

Since surge comments are passive, chaining the surge components is not a problem.

xprn | 2 comments | 3 weeks ago
Today I learned. I always thought it was some “electricity magic thing” like additional heat generated within the power strips causing issues between the connected devices, but this makes a lot more sense than whatever I was thinking of.

Although I do think I might have mixed some things up between regular power strips and those outdoors/industrial ones with a long (double/triple digit meter) rollable cable which my dad was a big user of back when he used to work in construction. Basically back when I was little he used to tell me never to plug power tools into a rolled-up “power wheel”, and I think that when I was later heard you shouldn’t daisy chain power strips I must have made that (wrong) connection.

willis936 | 1 comment | 2 weeks ago
Surge protectors do have one magical electrical thingy in them: metal oxide varistors (MOVs). They're what shunt current in an overvoltage transient and they do age with usage.
aceazzameen | 2 comments | 2 weeks ago
I've always known surge protectors age and eventually stop protecting from surges. But what I always wanted to know is how can you tell when it expires? I'm assumings it's based on how good/bad/stable the electricity is in your area. But still, is there any way to know when it's time to replace?
malfist | 1 comment | 2 weeks ago
Typically surge protectors have a little light to let you know if the surge circuitry is still good. Others will fail safe, meaning the won't power on if the circuitry is bad. Cheap ones may do neither.

Either way, if your house has had a surge and other equipment has died that wasn't surge protected, probably a good time to replace all surge protectors in the house, they're not really meant to survive multiple large surges. They shunt the power destructively, just somewhere you don't care.

neilv | 0 comments | 2 weeks ago
> they're not really meant to survive multiple large surges. They shunt the power destructively, just somewhere you don't care.

Is this a concern when buying used rackmount power conditioners (like used for live music setups?), to protect home IT gear? Can they be worn out without a sign that they are?

cesarb | 0 comments | 2 weeks ago
What I've read is that their main failure mode is that, as they age, their trigger voltage gets lower and lower, and at some point the normal line voltage is enough to trigger them all the time. And when they overheat, either due to being triggered all the time or due to diverting a large surge, they fail open and no longer have any protective effect on the circuit. High quality surge suppressors would have fuses physically touching the MOVs, so that when a MOV overheats and fails, the fuse opens and cuts power to the now unprotected output.
vbezhenar | 0 comments | 3 weeks ago
It's about heat. Cable has some resistance and emits heat. This heat has to dissipate somewhere. If cable is rolled out, it'll dissipate heat to the air. If "power wheel" is not rolled out, cable will heat cables around. Outer cables will dissipate heat to the air, but inner cables will not. So with enough current and enough time, this thing will melt.

You probably won't have issues charging iPhone from this thing or powering something for few seconds, so no need to go crazy about it, just something to keep in mind.

kosma | 2 comments | 3 weeks ago
It's not very different from daisy chaining normal extension cords - safe if you know what you're doing (not exceeding the current rating on any of them). Most surge protectors are fused, making them safer to daisy-chain than normal extension cords.
quickthrowman | 1 comment | 2 weeks ago
> It's not very different from daisy chaining normal extension cords - safe if you know what you're doing

It’s not safe, and it’s expressly forbidden by the NEC, see 11.1.5 below:

> 11.1.5 Extension Cords

> 11.1.5.1

> Extension cords shall be plugged directly into an approved receptacle, power tap, or multiplug adapter and shall, except for approved multiplug extension cords, serve only one portable appliance.

Daisy chaining extension cords is unsafe and not recommended. Only use extension cords that you’ve inspected and are properly rated for the environment (don’t use indoor cords outside, don’t use an outdoor extension cord outdoors unless it’s GFCI protected) and power usage of the device you are powering.

Any time electricity has to flow through a splice or mechanical connection, the possibility of a loose connection causing an arc and subsequent fire exists.

It’s unlikely to happen to you specifically, but it does happen and avoiding electrical fires is a good thing if it can be avoided.

Daisy chaining power strips is also forbidden by the NEC:

> 11.1.4.2

> The relocatable power taps shall be directly connected to a permanently installed receptacle.

dvdkon | 3 comments | 2 weeks ago
Yes, there is a risk of failure involved with anything electrical, but I don't see why anyone would consider chaining extension cords inherently dangerous enough to ban. It increases the number of connections, but that's a miniscule risk compared to the 5+ connections an extension cord might have on its own. The only significant risk I know is people disregarding the max amperage rating of everything in that chain.

For anecdotal experience, I've had both extension cords and wall plugs fail (nothing serious thankfully, but they did get a bit melted), but in those cases it had nothing to do with my extension cord chains, but rather an internal connection failure.

marcosdumay | 1 comment | 2 weeks ago
AFAIk, the rationale for extension chords is that they are sized to cause a controlled amount of voltage drop within their lenght. If you keep adding them, you will increase the drop, and many devices will react by increasing the current.
quickthrowman | 0 comments | 2 weeks ago
This is correct. For a 120v 12FLA load at a distance of 50’, you’re fine using a #14 cord. If you double that to 100’, you need to use #10 cord to account for the voltage drop. As voltage drop increases, the amount of current flowing through the cord increases, which can potentially heat up the insulation beyond its rated temperature.
fbdab103 | 0 comments | 2 weeks ago
It is probably one of those little process changes to minimize chance of catastrophic failure. Sure, the risk of the daisy chained system going poof is low, but not zero. Instead, you should try to re-work your plans so you do not need to daisy chain.
sgarland | 0 comments | 2 weeks ago
As an aside, increasing the length of extension cords can cause premature failure of some devices (mostly motorized tools, especially cheaply-made ones) if the wire gauge is inadequate, due to voltage drop.

As a general rule, I wouldn’t run tools past 50 feet on anything smaller than 12 AWG (and really, 14 AWG is the smallest I’d go for any length; anything smaller isn’t safe for most loads).

quickthrowman | 0 comments | 2 weeks ago
It’s not OK, it’s a violation of the NEC:

> 11.1.4.2

> The relocatable power taps shall be directly connected to a permanently installed receptacle.

A surge protector is a ‘relocatable power tap’ and must be plugged into a permanent receptacle.

willis936 | 4 comments | 3 weeks ago
You are not supposed to. The upstream device is sized for a maximum current and daisy chaining can lead to a scenario where downstream devices are sized for larger current than upstream devices, which is avoided everywhere else in electrical distribution.

So it's fine as long as you control the strip and keep track of loads (e.g. you know your spouse will never plug a vacuum into that handy receptacle you have there), but at work your EHS team will mark you down for it.

xtqv | 0 comments | 3 weeks ago
Daisy chaining is irrelevant to the problem that you can buy 18ga "lighting-only" extensions that bear a 15A rated NEMA 15R but are limited to 8A.

Daisy chaining a power bar with it's own circuit breaker can be ideal if it prevents someone from making the mistake of using a circuit in a way that trips a panel breaker, ie preventing your spouse from plugging a vacuum into a circuit shared by several rooms.

ta1243 | 1 comment | 2 weeks ago
In the UK, if I have a 6 way strip sized for 10A, which thus has a 10A plug in, I could then plug in a 4 way strip downstream with a 5A fuse, then a lamp with a 3A fuse, and that's fine. I could even connect it the other way.

If I plug in a heater pulling 10A then sure, the 5A fuse will blow.

Daisy chaining multiways will increase the resistance in the earth wire which could mean you end up with a class 1 device with a fault connecting live to earth which would only punting say 8A to earth due to a high resistance (but then your circuit's RCD would trip with that), but is it a major problem?

With the US system, do you not have wires capable of 3A (say 24 AWG) which you can connect to a normal socket which also takes a 10A vacuum?

If that lamp has a fault where it pulls 6A, what protects the 3A wire -- i.e. there's a fault with your lamp which is plugged into a 15A circuit breaker, and the lamp draws 10A, it wouldn't trip the breaker, and that nice thin 3A lamp cord would melt.

t0mas88 | 1 comment | 2 weeks ago
That lamp example happens nearly everywhere except the UK, due to the UK having fuses in plugs. We don't have that in the rest of Europe for example.
ta1243 | 2 comments | 2 weeks ago
So people are happy plugging in cabling into a circuit with no protection?
namibj | 1 comment | 2 weeks ago
There is protection, just not at the cable itself.

UK only needed to introduce that because of their ring main architecture, which was fused at levels above a plug.

Also c.f. extension coils and pre-battery vacuums: both needed their cable full unspooled to reach their full load rating. Yet they typically lack technical enforcement mechanism to not rely on users being literate and willing enough to RTFM.

ta1243 | 1 comment | 2 weeks ago
What provides protection for a 3A cable plugged into a 15A outless?
t0mas88 | 0 comments | 2 weeks ago
Safety margins in what you call a 3A cable. And each circuit being fused at a lower 16A, not the 30A that my British house had.

Something like 1.5 mm2 (only a 0.5mm diameter) is able to handle 12A if the insulation survives heating up to 60 degrees and 18A if 70 degrees is acceptable. The whole circuit would have a 16A fuse at the fusebox, so you're not going to get to 70 degrees.

Far from ideal, but also very very unlikely. Because a short would be over 16A and blow the fuse. So we're talking about some situation that's far from a normal load (any device that's close to such a load would need a different cable to be certified), while still remaining right under the maximum load of the fuse that's covering the circuit.

Homes aren't burning down all over the rest of Europe all the time, while fuses in plugs aren't a thing here.

Modified3019 | 0 comments | 2 weeks ago
It’s less about being happy about it, and more about ignorance, industry/legal inertia, and the complete lack of me being the global benevolent dictator for life. Sure some might initially resist my efforts, but they’d come around after receiving an appropriate reeducation at my fire safety camps.
vasco | 0 comments | 3 weeks ago
In your example there's a first undersized UPS A, then another UPS B, then whatever combination of electrical devices which power usage exceeds UPS A. You say this is problem.

If you have said combination of electrical devices, and if you're assuming we're using an undersized UPS A + the combo of devices, why does the UPS B matter?

If you're going to overload the UPS A you're going to overload the UPS A regardless of UPS B, no? Daisy chaining or not, that doesn't seem like the actual problem to a knee-jerk thinking.

4gotunameagain | 0 comments | 3 weeks ago
This is not specific to surge protection, but extension cords in general.
immibis | 4 comments | 2 weeks ago
"surge protector" is what Americans call a passive device that splits one outlet into several, yeah?

The danger is overloading. Back in the days when the main things you plugged in were incandescent lights and space heaters, this was probably a big issue. With computer equipment and LED lights you have to have a lot more stuff - many outlets' worth - to reach the circuit's maximum capacity.

If the circuit and "surge protectors" are rated for 1800W (15 amps x 120V), officially you should limit yourself to 80% of that for continuous loads which is 1440W, so you can supply 14 laptops or small small desktops that use 100W each, or over 200 raspberry pis on USB chargers that use 5W each, and either way you're going to need a lot of outlets before you come anywhere close to that limit.

At least that's a rough estimate. Power factor could decrease that number by up to 50% and you can use the full rating for intermittent loads; I'm not certified to know the fine print. Point is that 10 computers can easily use less power than a single space heater.

callalex | 1 comment | 2 weeks ago
>surge protector" is what Americans call a passive device that splits one outlet into several, yeah?

Not necessarily. There are “power strips” which turn one receptacle into several. Then there are sure protectors which are typically built into power strips. So not all power strips are surge protectors but almost all surge protectors are also power strips.

cesarb | 0 comments | 2 weeks ago
> So not all power strips are surge protectors but almost all surge protectors are also power strips.

There are panel-mounted surge suppressors (which can protect all circuits coming from the panel), and also inline surge suppressors with a single output like this one: https://www.lojaclamper.com.br/dps-iclamper-pocket-2pinos-10...

wnoise | 0 comments | 2 weeks ago
> "surge protector" is what Americans call a passive device that splits one outlet into several, yeah?

Technically different, but often combined functions. The splitting bit is a "power strip", or sometimes a "power bar". The surge protection is switching off when there's a short or overvoltage in the supply, or other larger than expected power draw.

m463 | 0 comments | 2 weeks ago
power switch = just connection to multiple outlets

surge protector = a device with electrical circuitry to help protect angaist surges and spikes.

https://en.wikipedia.org/wiki/Surge_protector

jcalvinowens | 0 comments | 2 weeks ago
> or over 200 raspberry pis on USB chargers that use 5W each

Those little switcher bricks are horribly inefficient: the 15W one I just pulled out of a drawer draws 0.8A on the primary. Realistically you're going to max out a 15A circuit around 20-30 of those, not 96 (1440/15).

vbezhenar | 0 comments | 3 weeks ago
As long as you keep load below threshold, I don't see any potential issues.
rinron | 0 comments | 2 weeks ago
probably because it Depends, If you dont know its safer not to. long answer (keep in mind i live in canada, im not a professional, this is just what i learned and trust, keep in mind above) - As long as no wire/bar exceeds its max Amp your safe no matter how many things are plugged in or how long of a daisy chain, the max amp is usually listed. - all devices should list the max amp they use, add up the amp's of all the devices connected to that wire and if its below your safe. - if your breaker is 15 amp, virtually all normal extensions/power bars are rated for at least 15 amps which means doesnt matter what you do the breaker should* flip before any damage is done - if breaker is above 15 amp most surge protectors have protection that will trigger if they exceed their max, most basic "splitters" and extension cords dont, eg if they dont have a switch or reset button they are pretty much guaranteed to not have this protection, be extra carful how much you load on those. some good rules of thumb to keep in mind, look for imprints or labels that list amps, smaller wires can handle less, damaged wires can handle less then they did before and shouldn't be used, if a wire or connector warms when its in use its overloaded reduce the load on it, especially if it warms quickly. here is a video that i liked that talks about it as well https://www.youtube.com/watch?v=K_q-xnYRugQ
dreamcompiler | 0 comments | 2 weeks ago
The reason it's a "bad idea" is that most surge protectors are power strips and you must be cautious when you daisy chain power strips. Likewise extension cords.

Why? Two reasons: You have to ensure the wire gauge on every link can handle the current, and at every junction (plug) the resistance is higher than in the wire itself. When electrical fires start they usually start at these plug junctions because they overheat.

The surge protectors themselves don't mind being daisy chained.

orblivion | 2 comments | 2 weeks ago
This is funny, I actually am wondering about plugging a surge protector into a UPS. I have some equipment (probably not very high power draw but I can confirm) conveniently zip tied to a peg board along with a power strip that I assume has a basic surge protector on it. One power cord leaves the whole thing, which is very clean, but power goes out a surprising amount here. Can I plug this whole thing into a UPS or should I find a replacement strip without a surge protector?
radicality | 0 comments | 2 weeks ago
From what I remember reading, you should not do that. Only plug in PDUs or directly connect equipment to a UPS. You’re meant to put the surge protection before the UPS. I think it’s because the circuitry in surge protectors can mess with what the UPS thinks the actual load is.

I believe some UPS brands might also void parts of your warranty if you use them with a surge protector plugged in.

https://www.apc.com/us/en/faqs/FA158852/

Eisenstein | 0 comments | 2 weeks ago
You can plug it in. The problems with the UPS being plugged into another UPS are related to the internal batteries and the inverters, not to the surge protection. Just don't plug in too many things and overload the UPS.
4gotunameagain | 1 comment | 3 weeks ago
yes, as they are passive device unless in the case of a surge, which would be shorted to ground by the first one in the row (technically, the first one whose limits are lower than the surge)
kosma | 2 comments | 3 weeks ago
The nature of surges is not simple like that - a lightning strike can easily blow MOVs and inrush limiting resistors in multiple devices. I come from a rural area and coming to someone's house with a bag of fresh MOVs and resistors is not an uncommon thing after a big storm.
4gotunameagain | 0 comments | 3 weeks ago
I believe that it highly depends on the type of the surge protector, their ratings and the cable network involved. I do not think that it would cause issues in two surge protectors from power outlets connected in series, and depending on their rating and switching characteristics maybe both could trigger, I agree.
numpad0 | 0 comments | 3 weeks ago
I believe the question is if it's safe at all to do so rather than whether the protection works or not, though I'd have to be all ears about interactions between multiple parallel surge arrestors.
necovek | 2 comments | 2 weeks ago
This is the type of article I find useless.

It would be great if Eaton went to the trouble to explain what exact conditions the two UPSes need to fulfill to be successfully daisy chained, which would probably put people away from doing it anyway.

But it would also be a much more informative article, and also positively framed, which is always a much better read.

deadbunny | 1 comment | 2 weeks ago
That just leads to "I followed your instructions on your website and my house burned down". No company is going to open themselves up to that.
necovek | 0 comments | 2 weeks ago
I know US is very litigious, but I am certain there are plenty of knowledge-based articles by companies in the US of A that could theoretically be tested in court this way, but really, aren't.

I mean, look for any mention of "slow-roast it for 12 hours" in your favourite web search engine (I notice a couple of those say "overnight", yikes).

zootboy | 2 comments | 2 weeks ago
They don't explain it because it basically never makes sense to daisy-chain a UPS. If you want redundancy in your power supply chain, use a dual-PSU computer. If you want longer backup times, get a UPS with a bigger battery.
BuildTheRobots | 0 comments | 2 weeks ago
The only time I think it makes sense if if you're doing a belt+braces with colo'd stuff in a datacentre.

The DC will have its own UPS system, but in the event it all goes wrong (which happens more often than I'd like) you probably want something in your cab that can give your equipment notification and time to shut down safely, and provide surge suppression and maybe some level of isolation from the inevitable back-emf caused by the rest of the hall going dark.

necovek | 1 comment | 2 weeks ago
That's still not saying much, unfortunately — you are going with "authoritative" vs "informative" argumentation ("trust me" instead of "this is why").

Explaining what are the conditions that need to be met for one UPS not to cause issues to another daisy chained off of it would help the reader understand why that's a bad idea.

zootboy | 1 comment | 2 weeks ago
The main technical reason is that the vast majority of UPSes cannot take what they give. If you have a 1000 VA UPS that is loaded at or near 1000 VA, it will draw significantly more than 1000 VA during periods of recharging, or if you make use of the non-protected outlets on certain models, or if the model is a double-conversion type. Thus, daisy-chaining two identically-sized UPSes will never work; they always need more input power capacity than they can output.

Then there's the issue of output waveform. Cheaper UPS models put out a hideous square wave or modified square wave waveform. This is adequate for being fed into a PC's PSU to be turned right back into DC, but most UPS line status detectors will not be happy being fed in such a bad waveform and will consider the grid faulted. Thus, as soon as you have an outage, both UPSes will go into battery mode, and you will not be able to use the "upstream" UPS's capacity. I suspect that even nicer UPSes may have issues accepting the power generated by another UPS, as their voltage and frequency regulation may not be good enough to satisfy the grid stability tests.

But the larger part of my reasoning for why you shouldn't daisy chain UPSes is that it's attacking the problem of reliability from the wrong angle. By daisy chaining UPSes, you have added an additional single-point-of-failure to your system. If instead you used a redundant PSU, you would have decreased the number of single-points-of-failure.

In my personal experience, I have seen far more power supplies die than I've seen UPSes, so the first thing I would do if I wanted a more reliable power setup is go for the redundant power supply. Only then would I consider attaching multiple UPSes (but I probably wouldn't under normal circumstances).

Dylan16807 | 0 comments | 7 days ago
> The main technical reason is that the vast majority of UPSes cannot take what they give. If you have a 1000 VA UPS that is loaded at or near 1000 VA, it will draw significantly more than 1000 VA during periods of recharging, or if you make use of the non-protected outlets on certain models, or if the model is a double-conversion type. Thus, daisy-chaining two identically-sized UPSes will never work; they always need more input power capacity than they can output.

It really depends on the model. The UPS I have takes uses barely any watts to recharge over a period of multiple hours.

lucumo | 2 comments | 3 weeks ago
What a stupid article. It doesn't tell you anything beyond "no, buy our products instead". WHY is it bad? HOW does it fail?

I mean, it's possible that I don't know enough about UPSes to understand the finer details and all this would be obvious to someone who does. But presumably they already know why it's a bad idea, and don't need this particular article to explain them.

The amount of scare words and the lack of detail honestly make me believe it probably IS okay to do, and Eaton just wants to scam some extra money out of people. It's just the posts in this thread that make me take it slightly more seriously.

tssge | 1 comment | 2 weeks ago
>Eaton just wants to scam some extra money out of people

Seems quite improbable that would be the purpose of the article. The article is basically saying "buy a single UPS instead of buying two to daisy chain them expecting to get better results". If anything, such advice would lead to people buying less devices.

Of course if one had two UPSes laying around for nothing, then I guess daisy chaining might come to mind to get better capacity or something for no extra price. However, generally people don't randomly have UPSs laying around for no reason, so it would make sense to buy higher capacity UPS than two lower capacity UPSs to daisy chain them anyways (and for probably quite similar total cost of ownership).

nixpulvis | 0 comments | 2 weeks ago
Let’s say I do have two UPSs lying around though, and a soldering iron.
pixl97 | 1 comment | 2 weeks ago
>make me believe it probably IS okay to do

Yea, as someone that ran their own micro ISP for a while, and worked for larger ISPs, no it's not ok to do at all. APC brand was the absolute worst about immediately tripping when plugged into another UPS. Eaton online UPS' actually handled it ok in comparison, but they are typically pretty expensive units.

This is definitely a case of the vendor attempting to save you money. Get an ATS on anything that doesn't accept dual power.

tssge | 0 comments | 2 weeks ago
>APC brand was the absolute worst about immediately tripping when plugged into another UPS.

At least from my experience of owning multiple APC UPS devices, they have a customizable acceptable power quality setting. In such cases setting them to accept the absolute worst quality of power could probably stop them from tripping on bad power input.

No idea if this affects the end devices, however there's probably a reason other than simply extra profit for the default power quality tolerance setting on those devices. Generally they are set to rather low tolerance threshold as the expected usage scenario is servers and other relatively sensitive equipment.

The models I own aren't really the most expensive either, some of the lower end tower models and they still have configurable acceptable power input settings available. Regarding them tripping on bad input and being "absolute worst", I consider this tripping a feature more than an anti-feature, especially as it is user configurable.

EDIT: Also wanted to add that it is actually _preferable_ for UPS to trip as immediately as possible on bad power input. That is the only purpose of such product after all: to protect the devices attached to it from bad or otherwise inadequate power input.

dusted | 0 comments | 2 weeks ago
Interesting. I'm sure it's correct, but it makes me wonder about the output quality of these devices. If the output of an UPS is so significantly different from regular utility power that it's unsuitable as input for an UPS, then it must be of a worse quality and unsuitable for the expensive equipment it's supposed to power ?

I do understand the logic that chaining UPS will cause interesting things to happen when power is restored and the downstream UPS can then overload the upstream UPS because it will incur additional load when charging its battery, which could trigger overload protection in the upstream device.

madaxe_again | 4 comments | 3 weeks ago
I mean, it is ok, as long as everything is appropriately sized - I live entirely off grid, with several battery banks and inverters, which are essentially giant UPSs - and have regular UPSs for various equipment so that when I shut the power down for whatever reason the network and servers stay up.
lambdaone | 0 comments | 3 weeks ago
There are a vast number of problems that all can be summarized as "this is a really stupid thing to do, unless you really know what you are doing". This is one of them.
geor9e | 1 comment | 2 weeks ago
This article is about daisy chaining UPSs into each other's AC outputs. I hope you're not doing that off grid. Daisy chained UPS means the energy takes the path of DC battery > AC inverter > DC rectifier > different DC battery > AC inverter > DC rectifier to whatever device you're powering. You could be losing up to 20% of the energy (server uptime) at each step of the daisy chain. And since there's only one path for power to take, if anything fails, it all goes down. The article's solution is super simple, just use them in parallel instead.
madaxe_again | 1 comment | 2 weeks ago
UPSs typically operate in passthrough mode unless a deviation in supply occurs - so no efficiency loss day to day - and no, I don’t chain UPSs, but as I said, the house batteries are essentially big damn UPSs.

Also, not particularly caring about efficiency currently as we always have more energy than we can use, and I’m currently looking at filling a shipping container with sand as a dump.

geor9e | 0 comments | 2 weeks ago
>UPSs typically operate in passthrough mode

Oh, that makes a lot of sense. In that case, daisy chaining two sounds like no big deal.

>filling a shipping container with sand as a dump

That's pretty cool. I didn't know private folks were doing that.

K0balt | 1 comment | 2 weeks ago
Same here, I run a lot of different equipment on grden variety UPS's on our solar grid - but that is fed by redundant 18KW three-phase inverters and 72KWH of batteries... so that probably looks a lot like utility power from the perspective of the UPS's.

Overall, the discussion tangentially reminds me of a common theme in aviation - twin vs single engine aircraft. With two engines, the chance of having an engine failure at a critical time is doubled.

immibis | 1 comment | 2 weeks ago
But you also have a good chance to get through the failure with one working engine. A two engine plane with one working engine climbs slowly, and a one engine plane with zero working engines doesn't climb at all.
K0balt | 0 comments | 2 weeks ago
The problem is that fully loaded, many piston twin planes do not climb at all or can only descend slowly on one engine.

There is a saying about light piston twins…. The other engine will take you all the way to the scene of the crash. If you are willing to fly your light piston twin half full, you have great safety margins, but then you are paying twice as much to move less payload than a comparable single engine aircraft.

I should say that some piston twins are much better than others in this regard, but for many it seems the extra engine mainly hauls the weight of the extra fuel and airframe you had to add to carry it. Asymmetrical thrust adds a lot of drag.

Moving to turbocharged engines or turbines tends to improve things a lot, but even some big twins can’t climb with one engine. (C130 in a many configurations, for example)

I’m pretty sure modern designs are much better as a rule. Composite construction and power to weight ratios of modern power plants have pushed the numbers safely to the left of the tipping point.

This is a lot harder to achieve using 1930s technology engines and construction as found in many light aircraft built up into the 1980s. There’s only so much you can get out of an air cooled, low RPM carburated gasoline engine,and complex shapes in metal construction cost big in labor and weight.

dgacmu | 0 comments | 3 weeks ago
Not really. In your case, you probably have a very high quality pure sine wave inverter that's much larger than the individual UPSes, which will make the downstream UPSes mostly happy as long as you don't approach max load.

Many cheap inverters are not pure sine, and a UPS seeing this waveform may decide it needs to go to battery also.

Practically, a UPS also adds to the current draw, and many people may accidentally exceed the circuit limit because they only look at the useful load but not also the UPS charging load after a power failure ends.

NelsonMinar | 0 comments | 2 weeks ago
This page is SEO crap. A thin article with little technical content peppered with links to the company's own products.
CapitalistCartr | 1 comment | 2 weeks ago
The places I've worked on used multiple generators, more than was required to keep running. Home Shopping Network had 8, 5 of which would keep them on air. That's an extremely reliable backup.
toxic72 | 1 comment | 2 weeks ago
Can you share more about the Home Shopping Network's broadcast infrastructure - that's such an explored little nugget of the world I've never given any thought to before
CapitalistCartr | 0 comments | 2 weeks ago
This is 30+ years ago, they had a halon system. They had calculated the volume of the rooms, including the contents so as to not kill people while supressing fire. So making a hole in a wall, or adding/subtracting anything was a huge production.
nuker | 2 comments | 3 weeks ago
The main point against seems to be that downstream UPS will not like "simulated or modified sine wave" if upstream UPS is not producing "Pure sine wave". To be tested :)
boricj | 2 comments | 3 weeks ago
Another important point is that an UPS can produce huge surge currents, for example when switching from battery to utility. The upstream load goes from zero to the sum of both the protected load and the UPS charging its battery.

When daisy-chaining an UPS to another, the downstream UPS can easily overload and trip the upstream UPS because of that.

lucumo | 1 comment | 3 weeks ago
Wow. Your post is much more informative and clearer than the article. And it's only three sentences.
nuker | 0 comments | 3 weeks ago
> Another important point is that an UPS can produce huge surge currents, for example when switching from battery to utility.

It has not happened yet. If downstream UPS likes the source, it is not going to switch to battery, and battery charging will Not be happening because downstream UPS had it charged already long time ago.

effluvium | 0 comments | 2 weeks ago
An easy fix for that would be to put a surge protector between the UPSs. (Joke)

------------

I bought three UPSs, all them used independently; but I had to stop using all of them. They all had a capacitor whine that was driving me crazy.

dgacmu | 1 comment | 3 weeks ago
I've tested it before. TFA is correct, at least with the APC UPS I tried it with once. The apc ups went to battery and then turned off when out of battery.
nuker | 1 comment | 3 weeks ago
Thanks! But why they don't like it? UPS, as a black box, should harvest whatever energy is in the source, regardless is it sine wave or freaking square mess. Even DC or RF is present :) Why so picky?
boricj | 2 comments | 3 weeks ago
That's true to an extent for online UPSes, which converts from AC to DC and then from DC to AC, completely isolating the input current from the output, but these are the most expensive types of UPSes.

Your run-of-the-mill UPS is likely to either be offline, which forwards the input to the output, or line-interactive, which can compensate to an extent under or over voltage conditions with a regulator. If the input current characteristics are outside allowable tolerances, they can't compensate and must switch the load to battery to continue powering it.

nuker | 1 comment | 3 weeks ago
> Your run-of-the-mill UPS is likely to either be offline, which forwards the input to the output,

This one surely should "like" simulated sine wave as a source and don't drop to battery?

boricj | 2 comments | 3 weeks ago
An offline UPS will switch to battery if it doesn't like the input. What qualifies as acceptable input depends on the design and specifications of the UPS. If it expects a real grid-like sine wave and doesn't see one it will reject it, regardless if the load would like it or not.
nuker | 3 comments | 3 weeks ago
> If it expects a real grid-like sine wave and doesn't see one it will reject it, regardless if the load would like it or not.

But why would it require grid-like sine wave and not go along with whatever is the source, provided source can still be used to charge its batteries? I saw no answers yet, and this "why" is the very key to the discussion.

soneil | 0 comments | 2 weeks ago
There's a lot of compromise in UPS design.

For example, a common topology in offline UPS is that the inverter and the charger are the same circuit driven differently[0] - so you can't charge the battery while the inverter is carrying load. This is popular at the low-end because you have literally half as much UPS, but makes what you're describing impossible.

Another common issue at the low end is that the inverter isn't thermally sized to run non-stop, they know they can cut a corner because your battery presents a finite and known duty cycle.

There are ways around this, but at some point you end up fixing the wrong problem - eg, it's cheaper, safer, and more resilient to buy a transfer switch instead of uprating two UPS to be capable of daisy-chaining.

[0] https://patents.google.com/patent/US5302858A/en

numpad0 | 1 comment | 2 weeks ago
I think you're being gatekept. It's inconceivable that just no one knows why square and triangular waves don't pass as AC.
nuker | 1 comment | 2 weeks ago
I cannot tell without /s, but yes, who designs like this, lol
numpad0 | 0 comments | 2 weeks ago
It's not sarcasm. When nobody tells you a why item and you think that's because literally everyone else is dumber than you, it's likely there are odd numbers of sign errors in your heuristics.
nuker | 0 comments | 2 weeks ago
In other words. I asked if A should lead to B. You answered "A leads to Not B" :)
nuker | 1 comment | 3 weeks ago
> If the input current characteristics are outside allowable tolerances

This is the key to this whole discussion. I guess it boils down to existing line-interactive designs, why they can't work with simulated sine as a source.

dgacmu | 0 comments | 3 weeks ago
A transfer-switch based UPS still needs to protect against brownouts, so it too has line behavior parameters outside of which it will switch to battery. It's an interesting question if/why a modified sine wave input would trigger that or not. Probably one of those "it depends on the design" things. (modified sine -> approximately an oscillating square wave.)

A dual-conversion (online) UPS is almost certainly more robust as far as what kinds of inputs it can accept (though as GP noted, they're more expensive, and they're also less efficient due to the additional rectification->inverter).

Waterluvian | 0 comments | 3 weeks ago
I’m guessing the sine waves wouldn’t line up?

Edit: derp. Wouldn’t matter. I was thinking putting them in parallel.

elintknower | 0 comments | 2 weeks ago
Is anyone else here using Ecoflow batteries as a UPS backup? I really wish Eeaton would produce a similar consumer facing function that is intended to be used long-term 24/7 not just on weekend trips etc.
danjl | 2 comments | 2 weeks ago
Do kids these days actually make Daisy chains anymore? You know, with real Daisy flowers.
m463 | 0 comments | 2 weeks ago
I remember chewing gum wrapper chains made by tricky folding.
AzzyHN | 0 comments | 2 weeks ago
I was unaware that was the origin of the term, so probably not